Aluminium Windings - Dry Type Transformers 

By on

The other day I was talking to a colleague who is a building services consultant.  Despite regularly specifying dry-type/cast resin transformers he was unaware that many manufacturers use aluminium for the windings; I think Siemens exclusively use aluminium and don’t offer copper anymore.  To confirm this he promptly phoned Schneider Electric and was informed that they use aluminium (or copper on request).

This reminded me of a few years ago when I was working for a contractor and wanted to install Siemens transformers on a large international airport.  Siemens was one of the three preferred vendors; however the airport’s specification called for copper windings.  Because of the specification the airport refused the transformers for weeks (we even had the Siemens factory guys out from Germany).  The client’s agreement in the end was not driven by technical considerations, but by contractual/time delay issues.  Transformers were installed and as far as I know are still happily humming away.

The illustration of a Siemens GEAFOL transformer shows the HV and LV aluminium windings.  The HV windings are wound from aluminium foil interleaved with an insulating foil.  The LV windings are wound form single-aluminium sheets and interleaved with cast-resin impregnated fibreglass fabric. Foil type windings are subject to less electrical stress than conventional windings resulting in higher AC and impulse voltage withstand characteristics.  Thermal expansion coefficients of aluminium and cast resin are similar and resulting thermal stress due to load change is kept to a minimum.

To my mind, compliance with the performance requirements of the manufacturing standards is the important criteria and the constructional aspects (aluminium or copper) are not that significant. As a final practical tip, during the above airport installation copper cable was being terminated onto the aluminium terminals of the transformer.  In this instance bi-metallic plates were inserted between the cable lugs and transformer terminals.



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus

  1. ManjoloPhiri's avatar ManjoloPhiri says:
    9/1/2011 2:11 PM

    The only reason I would allow the use of Alluminium windings in a transformer is the price difference between copper and alluminum. Copper is the best material so far for transformer windings whatever electrical parameters you consider! Please transformer manufacturers continue using copper afterall the price is now down!

    • Steven's avatar Steven says:
      9/1/2011 2:11 PM

      My aluminium winding experience has been with Siemens because they only manufacture aluminium windings. Have to say that I have never had any problems and the transformers work great. Of course copper windings also work great (to me both are acceptable). Talking of problems and a bit off topic, I also think that when selecting a transformer it needs to be suitable for the intended environment/loading and that surge arrestors if used are correctly sized. I have recently come across an instance where this was not done and they have had several transformer failures.

  2. rommel's avatar rommel says:
    9/1/2011 2:11 PM

    Which material, element is more conductive? copper or aluminium?

    • Steven's avatar Steven says:
      9/1/2011 2:11 PM

      Copper is the better conductor. Although Aluminum is still pretty good as a conductor.

  3. Paul's avatar Paul says:
    12/28/2012 2:57 PM

    How the bi-metallic plates can eliminate the ionization potential between two type of metal?

    • Steven's avatar Steven says:
      1/13/2013 7:41 AM

      Bimetallic plates prevent corrosion which could result from a direct connection of two dissimilar metals (aluminum and copper in this case).


Comments are closed for this post:
  • have a question or need help, please use our Questions Section
  • spotted an error or have additional info that you think should be in this post, feel free to Contact Us



Random Numbers

Using laser optical pulses the random number generator utilizes the time between arrival of random photos to generate the numbers, ensuring true accuracy...

myElectrical - Cable Sizing Tool Upgrade

Our IEE cable sizing was wrote a few years ago and had become rough around the edges. I thought it was time to give the tool a service. Unfortunately when...

Induction Motor Equivalent Circuit

Induction motors are frequently used in both industrial and domestic applications.  Within the induction motor, an electrical current in the rotor is induced...

Motor Insulation

Insulation on a motor prevents interconnection of windings and the winding to earth.  When looking at motors, it is important to understand how the insulation...

Arc Flash Calculations

Working in the vicinity of electrical equipment poses an hazard. In addition to electric shock hazard, fault currents passing through air causes Arc Flash...

Copyright Infringement

myElectrical does not support or promote the use of copyrighted material without the copyright owner's consent. If you believe that material for which...

Tip – Latitude and Longitude on Large Scale Plans

If you are working on a large plan, get the real coordinates [latitude, longitude] for two or more points and add them to the drawing. That way you can...

How to Check a Circuit is Dead

If you want to check a circuit is dead (not live), you should always use the three point method. First check a known live circuit, then check the dead...

Fault Calculation - Per Unit System

Per unit fault calculations is a method whereby system impedances and quantities are normalised across different voltage levels to a common base.  By removing...

Fire Resistant and Fire Retardant Cables

Fire resistant and fire retardant cable sheaths are design to resist combustion and limit the propagation of flames. Low smokes cables have a sheath designed...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note